Barnard Hospital-Steam Service Interruption 9/28/2024

On Saturday, September 28th 6 am – 4 pm Facilities will shut off the steam to the entire building. Contractors will be replacing a steam vent on the eighth floor. Temperatures throughout the building may be cooler than normal during this time.

East Building, East Imaging Center-Fire Alarm Service Interruption 9/17/2024

On Tuesday, September 17th, 9 am – 12 pm, there will be a test of the Fire Alarm System. Audibles will be heard and strobes will be visible throughout the buildings during the test. The purpose of this test is for the City of St. Louis inspector. THIS IS ONLY A TEST

Biotechnology Center-Elevator Service Interruption 9/13/2024

On Friday, September 13th 6-8 am elevators #51 & #52 will be taken out of service so that contractors can complete some work in the elevator shaft for the modernization project. Please use the freight elevator #31 at the east end of the building during this time. Once the work is complete elevator #51 will […]

Mallinckrodt Institute Radiology-Fire Alarm Service Interruption 9/30/2024

On Monday, September 30th 4 – 10 pm Facilities will be conducting tests on the fire alarm system of the HVAC. There will be a controlled shut down of the air handlers, also the stair pressurization fan will run. THERE WILL BE NO AUDIBLES OR STROBES during this test.

Biotechnology Center-Domestic Cold Water Service Interruption 9/20/2024

On September 20th from 12 am to 7 am there will be no domestic hot and cold water to the Biotechnology Center. During this time there will be limited to no hot and cold water to the restrooms, autoclaves, washers, sinks, emergency eye wash and shower stations, vacuum system , and anything requiring hot or […]

COMPLETED-4511 Forest Park-Electric Service Interruption 9/10-17/2024

A deficiency was identified with the emergency back up generator for the electrical power systems in the building. In the unlikely event that the building were to experience a total electrical power loss from Ameren, the building will not have any backup power. Anything that runs on electric will not work. All HVAC climate control […]

CSRB North Tower Addition-Sprinkler System Service Interruption 9/20/2024

On Friday, September 20th 7 am – 3 pm the sprinkler system in the penthouse of CSRB-North Tower Addition will be drained due to contractors moving sprinkler lines for the project. The system will be monitored during this outage. The rest of the fire alarm system will be fully operational.